HANSENTEK AN104 SINGLE ZONE SPARK DETECTION SYSTEM | FIRE PREVENTION

The Hansentek AN104 is a value-priced, full-featured spark detection and extinguishment system designed specifically for facilities with a single dust collector. A single-zone spark detection and extinguishment control panel that provides ultra-fast fire hazard mitigation for industrial pneumatic ducts. The Hansentek AN104 is a value-priced, FM-approved spark detection and extinguishment system for single dust collectors. Features ultra-fast processing and NEMA 12 cabinet.

HANSENTEK AN104 SINGLE ZONE SPARK DETECTION SYSTEM | FIRE PREVENTION

The HANSENTEK AN104 is a micro-processor-based system that detects sparks or embers in pneumatic air ducts and instantaneously triggers a water spray curtain to extinguish them. It features sophisticated “Sensi-Check” through-the-lens sensitivity testing, allowing for regular maintenance without removing detectors from the ductwork. The system is field-configurable and supports standard, high-temperature, and explosion-proof detectors.

PRODUCT USES:

  • Pneumatic & Conveyor Transport: Extensively used where sawdust, cellulosic fibers, chemical dusts, pharmaceuticals, and food ingredients are transported.
  • Welding Fume Exhaust: Monitoring for smoldering particles in industrial ventilation systems.
  • Dust Collector Protection: Ideally suited for single dust collector facilities with one or two main pneumatic lines.
  • Fire Mitigation: Controls abort dampers, fan shutdowns, and auxiliary deluge systems.

 

 

 

Technical Sheets

Catalog Page

Specifications

HANSENTEK AN104 SINGLE ZONE SPARK DETECTION SYSTEM | FIRE PREVENTION
– KEY SPECIFICATIONS

  • Zone Capacity: Single zone, capable of protecting a duct up to 44″ in diameter.
  • Signal Processing Speed: Ultra-fast response time of less than 85 milliseconds.
  • Detector Response Time: Less than 60 microseconds.
  • Power Supply: Universal AC input (110–250 VAC, 50/60 Hz).
  • Water Supply Requirements: 50–100 PSI (3.5 to 7 Bar); capable of 19.5 US gallons per minute (74 LPM).
  • Air Velocity Operating Range: 500 to 10,000 feet per minute (2 to 50 m/s).
  • Cabinet Rating: Industrial NEMA 12 / IP54 rated enclosure.
  • Compliance: FM Approved (when used in a complete system) and CE marked.

 